R-Tech INV160 Guía de instalación Pagina 62

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 120
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 61
C-2
Electrical diagrams
Electrical interlocking by the IVE unit
Recommended electrical control system
DB101689
(1) The “normal” and “replacement” source transfer orders must be interlocked electrically.
(2) Operating diagram: the SDE “fault-trip” signals are transmitted to the IVE unit. The SDE
auxiliary contacts are mounted in the circuit breakers.
Legends
ON
“Normal” source opening order
OR
“Replacement” source opening order
FN
“Normal” source closing order
FR “Replacement”
source closing order
L1 “Normal”
source “fault-trip” signal
L2 “Replacement” source “fault-trip” signal
N “Normal”
source auxiliary wiring connector
R “Replacement”
source auxiliary wiring connector
Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.
Remote-operated
source-changeover systems
2 Compact NS100/1600 or
Masterpact NT/NW devices
Livre 1.indb 2 08/10/2008 18:39:39
Vista de pagina 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 119 120

Comentarios a estos manuales

Sin comentarios