A-15
Functions
and characteristics
DB101605
Downstream coupling accessory
This accessory simplies connection to bars and cables with lugs.
It may be used to couple two circuit breakers (Compact NS100 to 630) or switch-
disconnectors (Interpact INS/INV100 to 630) of the same size.
Pitch between outgoing terminals:
Interpact INS250 and INV100 to 250: 35 mm
Interpact INS/INV320 to 630: 52.5 mm
Compact NS100 to 250: 35 mm
Compact NS400 to 630: 52.5 mm.
For Compact NS circuit-breakers, the downstream coupling accessory can be used
only with xed versions.
Connection and insulation accessories
The coupling accessory can be tted with the same connection and insulation
accessories as the circuit breakers and switch-disconnectors.
b
b
b
b
Possible uses Downstream coupling
Possible Outgoing pitch
(mm)
Manual source-changeover systems
INS250 (100 to 250 A) with rotary handle b 35
NS100/250 with rotary handle b 35
NS
100/250 on base plate with toggle control b 35
INS400/630
(320 to 630 A) with rotary handle b 5
2.5
NS400/630 with rotary handle b 5
2.5
NS400/630 on base plate with toggle control b 5
2.5
Complete source-changeover assembly
INS250 (100 to 250 A) b 35
INS400/630 (320 to 630 A) b 5
2.5
Remote-operated source-changeover systems
NS100/250 b 35
NS400/630 b 5
2.5
Remote-operated
Connection and insulation accessories for
Compact NS and INS y 630 A